Thermo-pride OH5-85DE User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
All installations and services must be performed by qualified service personnel.
OH SERIES
MODEL NO. OH2 OH5-85 OH11-105 OH5-85DXE
HEAT INPUT RATE IN BTU/HR
70,000 106,250 126,000
85,000
106,250
HEATING CAPACITY IN BTU/HR
56,000 85,000 101,000
74,000
85,000
HEIGHT OF CASING
52” 56” 59-1/2” 56”
WIDTH OF CASING
19” 24” 24” 24”
DEPTH OF CASING
27” 33” 34” 33”
WARM AIR OUTLET
17 x 17 22 x 20 22 x 20 22 x 20
RETURN AIR INLET
18 x 14 23 x 14 25 x 16 25 x 16
DIA. OF FLUE OUTLET
5” 6” 6” 6”
FLOOR-CENTER OF FLUE
TOP TOP TOP TOP
FLOWRATE from .2” & .5” w.c.
EXTERNAL STATIC PRESSURE
COOLING COOLING COOLING COOLING
@2 TON SWITCH SELECTION (CFM)
800 800 800 726
@2-1/2 TON SWITCH SELECTION (CFM)
1000 1000 1000 924
@3 SWITCH SELECTION (CFM)
1200 1200 1200 1276
@3-1/2 TON SWITCH SELECTION (CFM)
1400 1400 1400 1474
4 TON
1600
HEATING HEATING HEATING HEATING
@70deg SWITCH SELECTION (CFM)
737 1134 1335
905
1121
APPROX TEMPERATURE RISE (°F)
70 70 70 72
70
BLOWER MOTOR HP
1/2 1/2 1/2 3/4
NOZZLE SIZE
.55 .75 .90 .70
NOZZLE SPRAY ANGLE PATTERN
80º Hollow 80º Hollow 80º Hollow 45º W
LARGEST RECOMMENDED
AIR CONDITIONER
3.5 Ton 3.5 Ton 3.5 Ton 4 Ton
SIZE OF FILTERS
20” x 16” 25” x 16” 25” x 16” 20” x 25”
NOTES:
1. Heating capacity based on annual fuel utilization efficiency rated by manufacturer.
2. On all outlet and inlet dimensions, the first dimension is width.
3. To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor speed is
required.
6. Electrical characteristics at 115 volts, 60 Hz., 1 phase (less than 15 amps, for all models).
2
Page view 3